<DocHeader>
<DocTitle>Planned Transmission Outages Occurring Next 4 to 6 Months</DocTitle>
<DocRevision>1</DocRevision>
<DocConfidentiality>
<DocConfClass>PUB</DocConfClass>
</DocConfidentiality>
<CreatedAt>2026-05-04T06:20:51</CreatedAt>
</DocHeader>
<DocBody>
<OutageRangeStart>2026-08-02T00:00:00</OutageRangeStart>
<OutageRangeEnd>2026-10-30T23:59:59</OutageRangeEnd>
<OutageRequest>
<OutageID>1-00113813</OutageID>
<PlannedStart>2026-07-06T08:00:00</PlannedStart>
<PlannedEnd>2026-08-14T18:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>EAR FALLS GS LAC SEUL SS1</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRequested>
<EquipmentName>EAR FALLS GS LAC SEUL T2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>115 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRequested>
<EquipmentName>EAR FALLS GS TSS1</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>Non-recallable</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00144538</OutageID>
<PlannedStart>2025-03-10T07:00:00</PlannedStart>
<PlannedEnd>2027-12-10T17:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>KAKABEKA FALLS GS T1</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRequested>
<EquipmentName>KAKABEKA FALLS GS T2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRequested>
<EquipmentName>KAKABEKA FALLS GS T3</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRequested>
<EquipmentName>KAKABEKA FALLS GS T4</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>Non-recallable</EquipmentRecallTime>
<OutageRequestStatus>AA</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00144692</OutageID>
<PlannedStart>2026-08-24T08:00:00</PlannedStart>
<PlannedEnd>2026-10-02T18:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>MANITOU FALLS GS TSS1</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRequested>
<EquipmentName>MANITOU FALLS GS TSS2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>Non-recallable</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00245787</OutageID>
<PlannedStart>2026-09-08T07:00:00</PlannedStart>
<PlannedEnd>2026-09-18T16:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>CHATS FALLS GS T30-Q4C</EquipmentName>
<EquipmentType>Disconnect</EquipmentType>
<EquipmentVoltage>230 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRequested>
<EquipmentName>CHATS FALLS GS TSS2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>1 Day(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00247165</OutageID>
<PlannedStart>2026-07-13T07:00:00</PlannedStart>
<PlannedEnd>2026-09-01T08:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>NANTICOKE TS 59-N582L</EquipmentName>
<EquipmentType>Disconnect</EquipmentType>
<EquipmentVoltage>500 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRequested>
<EquipmentName>NANTICOKE TS T13-HT13</EquipmentName>
<EquipmentType>Disconnect</EquipmentType>
<EquipmentVoltage>500 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>14 Day(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00247166</OutageID>
<PlannedStart>2026-10-23T12:00:00</PlannedStart>
<PlannedEnd>2026-10-23T16:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>NANTICOKE TS T13-HT13</EquipmentName>
<EquipmentType>Disconnect</EquipmentType>
<EquipmentVoltage>500 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>1 Hour(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00247612</OutageID>
<PlannedStart>2026-09-16T08:00:00</PlannedStart>
<PlannedEnd>2026-09-16T16:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>ARNPRIOR GS TSS1</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>1 Hour(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00247630</OutageID>
<PlannedStart>2026-08-24T08:00:00</PlannedStart>
<PlannedEnd>2026-08-28T16:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>ARNPRIOR GS TSS1</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>5 Day(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00247870</OutageID>
<PlannedStart>2026-09-24T08:00:00</PlannedStart>
<PlannedEnd>2026-09-24T16:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>STEWARTVILLE GS T4-D</EquipmentName>
<EquipmentType>Disconnect</EquipmentType>
<EquipmentVoltage>115 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRequested>
<EquipmentName>STEWARTVILLE GS T5-D</EquipmentName>
<EquipmentType>Disconnect</EquipmentType>
<EquipmentVoltage>115 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRequested>
<EquipmentName>STEWARTVILLE GS TSS2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>1 Hour(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00247871</OutageID>
<PlannedStart>2026-09-23T08:00:00</PlannedStart>
<PlannedEnd>2026-09-23T16:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>STEWARTVILLE GS TSS1</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>1 Hour(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00247875</OutageID>
<PlannedStart>2026-08-06T08:00:00</PlannedStart>
<PlannedEnd>2026-08-06T16:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>MOUNTAIN CHUTE GS SS1</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>1 Hour(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00247876</OutageID>
<PlannedStart>2026-08-05T08:00:00</PlannedStart>
<PlannedEnd>2026-08-05T16:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>MOUNTAIN CHUTE GS SS1</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>1 Hour(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00249610</OutageID>
<PlannedStart>2024-03-15T08:00:00</PlannedStart>
<PlannedEnd>2027-12-31T23:00:00</PlannedEnd>
<Priority>I</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>LAKEHEAD TS C8A</EquipmentName>
<EquipmentType>Breaker</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>INFO</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>Non-recallable</EquipmentRecallTime>
<OutageRequestStatus>IMPL</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00249892</OutageID>
<PlannedStart>2026-10-23T15:00:00</PlannedStart>
<PlannedEnd>2026-11-07T15:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>LOWER NOTCH GS SS1</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>4 Day(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00249893</OutageID>
<PlannedStart>2026-09-21T08:00:00</PlannedStart>
<PlannedEnd>2026-09-24T15:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>LITTLE LONG GS SS2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>8 Hour(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00249895</OutageID>
<PlannedStart>2026-09-14T08:00:00</PlannedStart>
<PlannedEnd>2026-09-15T15:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>SMOKY FALLS 2 GS SS1</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>6 Hour(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00249927</OutageID>
<PlannedStart>2026-08-24T08:00:00</PlannedStart>
<PlannedEnd>2026-09-03T15:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>SMOKY FALLS 2 GS SS2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>Non-recallable</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00249934</OutageID>
<PlannedStart>2026-07-13T08:00:00</PlannedStart>
<PlannedEnd>2026-08-21T15:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>LOWER NOTCH GS SS2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>4 Day(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00250625</OutageID>
<PlannedStart>2026-09-14T07:00:00</PlannedStart>
<PlannedEnd>2026-09-15T16:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>OTTO HOLDEN GS SS2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>Non-recallable</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00251598</OutageID>
<PlannedStart>2026-08-18T09:00:00</PlannedStart>
<PlannedEnd>2026-08-18T16:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>SMOKY FALLS 2 GS SS2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>15 Min(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00251600</OutageID>
<PlannedStart>2026-08-19T09:00:00</PlannedStart>
<PlannedEnd>2026-08-19T16:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>SMOKY FALLS 2 GS SS2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>15 Min(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00251601</OutageID>
<PlannedStart>2026-08-20T09:00:00</PlannedStart>
<PlannedEnd>2026-08-20T16:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>SMOKY FALLS 2 GS SS2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>15 Min(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00251893</OutageID>
<PlannedStart>2026-08-10T07:00:00</PlannedStart>
<PlannedEnd>2026-08-19T17:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>OTTO HOLDEN GS SS2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>2 Day(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00251926</OutageID>
<PlannedStart>2026-10-05T08:00:00</PlannedStart>
<PlannedEnd>2026-11-06T18:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>EAR FALLS GS TSS2</EquipmentName>
<EquipmentType>PowerTransformer</EquipmentType>
<EquipmentVoltage>50 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>7 Day(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00252399</OutageID>
<PlannedStart>2026-07-27T05:00:00</PlannedStart>
<PlannedEnd>2026-10-13T05:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>BRUCE A TS T27-E</EquipmentName>
<EquipmentType>Disconnect</EquipmentType>
<EquipmentVoltage>500 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>Non-recallable</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00259321</OutageID>
<PlannedStart>2026-08-09T05:30:00</PlannedStart>
<PlannedEnd>2026-08-21T15:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>BECK 2 TS TL21L24</EquipmentName>
<EquipmentType>Breaker</EquipmentType>
<EquipmentVoltage>230 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>2 Day(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00259671</OutageID>
<PlannedStart>2026-09-27T05:30:00</PlannedStart>
<PlannedEnd>2026-09-27T15:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>BECK 2 TS K2_BUS</EquipmentName>
<EquipmentType>Bus</EquipmentType>
<EquipmentVoltage>230 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>2 Hour(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00259672</OutageID>
<PlannedStart>2026-09-28T05:30:00</PlannedStart>
<PlannedEnd>2026-10-02T15:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>BECK 2 TS D2_BUS</EquipmentName>
<EquipmentType>Bus</EquipmentType>
<EquipmentVoltage>230 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>6 Hour(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00259673</OutageID>
<PlannedStart>2026-10-18T05:30:00</PlannedStart>
<PlannedEnd>2026-10-18T15:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>BECK 2 TS K2_BUS</EquipmentName>
<EquipmentType>Bus</EquipmentType>
<EquipmentVoltage>230 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>2 Hour(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
<OutageRequest>
<OutageID>1-00271694</OutageID>
<PlannedStart>2026-10-18T08:00:00</PlannedStart>
<PlannedEnd>2026-11-01T08:00:00</PlannedEnd>
<Priority>P</Priority>
<Recurrence>C</Recurrence>
<EquipmentRequested>
<EquipmentName>LAMBTON TS T6-P1</EquipmentName>
<EquipmentType>Disconnect</EquipmentType>
<EquipmentVoltage>230 kV</EquipmentVoltage>
<ConstraintType>OOS</ConstraintType>
</EquipmentRequested>
<EquipmentRecallTime>6 Hour(s)</EquipmentRecallTime>
<OutageRequestStatus>STDY</OutageRequestStatus>
</OutageRequest>
</DocBody>